← Back to Home Hub← Back to Products, Industry and Workplaces

Firefighting Foam & PFAS

The chemistry of historical foam formulations, how releases affect investigations, and why foam and protective gear are different exposure questions.

In this entry
  1. Why foam chemistry matters
  2. AFFF was never just PFOS
  3. A limited test sees a limited mixture
  4. How use becomes a release
  5. Foam and turnout gear are different sources
  6. Changing foam also means managing the equipment
  7. Sources

Why foam chemistry matters

Firefighting foams serve different fire hazards. Class A foams are used for materials such as wood and vegetation. Class B foams address flammable liquid hazards. Aqueous film forming foam, or AFFF, is a fluorinated Class B product developed to spread a thin water based film over fuel. Alcohol resistant formulations address additional challenges from certain fuels.

Foam performance, chemical composition and environmental impact are separate questions. The term firefighting foam alone does not identify PFAS content. A product’s formulation and intended application matter, and historic requirements do not establish which products a department must use today. [1]

AFFF was never just PFOS

In 2012, Benjamin Place and Jennifer Field identified ten fluorochemical classes in seven historical military certified formulations. The mixtures included negatively charged, positively charged and mixed charge surfactants. Surfactants are substances that change how liquids interact with surfaces, helping explain why they were useful in foam.

Two manufacturing approaches shaped historical formulations: electrochemical fluorination and fluorotelomer chemistry. Their products differed. Treating every foam as a container of PFOS overlooks other ingredients and the chemicals those ingredients can become. A brand name, approximate date and product record can help an investigator identify the relevant formulation history. [2]

A limited test sees a limited mixture

Historical AFFF can contain several fluorinated ingredients, including precursors. Testing only PFOA and PFOS therefore asks a narrower question than identifying the formulation. The product analysis described above used chemistry directed at ingredients that routine water testing could miss.

For an environmental investigation, the method needs to match the question. Targeted testing quantifies its named compounds. Precursor assays and broader chemical screening can add information, but they have their own limits and do not provide a complete inventory of every formulation. [2] [4]

How use becomes a release

Foam concentrate is diluted with water before application. Fire response, equipment testing, training and leaks can all introduce that mixture into the environment. Drains, pavement, containment and nearby soil influence where it travels.

An investigation connects those routes with the product and use history. Containing and collecting a discharge changes its immediate pathway, but the collected foam and wastewater still need appropriate management. Nearby fuel contamination can complicate the site: treatment designed for fuel does not automatically remove PFAS or leave their chemical pattern unchanged. [1]

Foam and turnout gear are different sources

Firefighters may encounter PFAS in foam and in protective materials. A 2023 NIST investigation measured 53 selected PFAS across 20 new turnout gear textiles. The moisture barrier and outer shell generally contained more measured PFAS than thermal liner materials. That finding concerns the equipment itself, even before a fire.

The study did not measure how much entered a firefighter’s body. Detecting PFAS in fabric identifies a potential source, not an absorbed dose. Distinguishing foam ingredients from gear treatments helps researchers avoid assigning every blood measurement to whichever source is most familiar. [3]

Changing foam also means managing the equipment

Replacing foam involves the stored product and the system that held it. Residues can remain in tanks, pipes and equipment. Cleaning and replacement work can generate contaminated rinsate, meaning liquid produced during cleaning, that needs to be collected and managed.

A replacement also needs to meet the fire protection requirements for its intended use. Product selection, compatibility, cleaning, testing and waste handling are connected decisions. Switching products does not remove PFAS already released to soil or groundwater. Those historical releases remain a separate environmental investigation. [1]

See the work

BURNED: Protecting the Protectors

This documentary follows concerns about PFAS and firefighter protective equipment. Gear and firefighting foam are different potential sources, a distinction that matters when watching the film.

Ethereal Films

Watch at the original publisher (opens a new tab)

Read the sources

PFAS USA